26
Operation Section
&AN-ODE#ONTROL3WITCH
Ê ÊÊ Ê ÊÊÊ Ê UÊ /iÊ v>Ê ÌÀÊ «iÀ>ÌÊ ÃÊ VÌÀi`Ê LÞÊ Ài>ÞÃÊ Ê ÌiÊ Ài>ÞÊ L>À`Ê ÌÀÕ}Ê >Ê VÀ«ÀViÃÃÀÊ
the control panel assembly. The fan program in the microprocessor can be changed by a DIP
switch on the left side of the relay board located in the control box.
Ê ÊÊ Ê ÊÊÊ Ê UÊ/iÀiÊ>ÀiÊÌÜÊÃiÌÌ}Ã\
(1) Cool to stop
Ê ÊÊ Ê ÊÊÊ Ê UÊ 7iÊ ÌiÊ *Ê ÃÜÌVÊ ÃÊ ÃiÌÊ Ê ÌiÊ `ÜÜ>À`Ê ÀÊ -/"*Ê «ÃÌ]Ê ÌiÊ VÀ«ÀViÃÃÀÊ VÌÀÃÊ Ìi
fan motor using the same room temperature thermistor that it uses to control the compressor. In
this case, both the fan and the compressor stop when the microprocessor receives a sufficiently
low intake air (room temperature) signal from the thermistor (equal to or less than the set point).
When the temperature increases (exceeds the set point) the microprocessor restarts the fan and
compressor automatically. However, if the unit has been off for less than 120 sec, the fan starts
before the compressor (time delay feature).
(2) Cool to operate
Ê ÊÊ Ê ÊÊÊ Ê UÊ7iÊ ÌiÊ *Ê ÃÜÌVÊ ÃÊ ÃiÌÊ ÌÊ ÌiÊ Õ«Ü>À`Ê ÀÊ "*,/Ê «ÃÌ]Ê ÌiÊ VÀ«ÀViÃÃÀÊ VÌÀÃ
the fan operation using control panel inputs only. The fan operates continuously during fan only
and cool modes. (This is the factory default setting.)
4EMPERATURE3CALE$ISPLAY3WITCH
Ê ÊÊ Ê ÊÊÊ Ê UÊ7iÊ ÌiÊ *Ê ÃÜÌVÊ ÃÊ ÃiÌÊ Ê ÌiÊ `ÜÊ ÀÊ ºc»Ê «ÃÌ]Ê ÌiÊ ÃiÌÊ «ÌÊ >`Ê ÀÊ Ìi«iÀ>ÌÕÀiÊ >Ài
displayed in degrees Celsius. “°C” is indicated on the LCD. When the DIP switch is set in the up
or “°F” position, the set point and room temperature are displayed in degrees Fahrenheit . “°F”
is indicated on the LCD. (This is the factory default setting.)