24
Operation Section
$RAIN3WITCH
&OREVAPORATOR
UÊ/iÊ"vwViÊ*ÀÊÎÈÊÃÊiµÕ««i`ÊÜÌÊ>Ê`À>ÊÌ>ÊÃÜÌV°Ê7iÊÌiÊ`À>ÊÌ>ÃÊ>VVÕÕ>Ìi
approximately 8.0 gal (30 L) of condensate (water) in the drain tanks, the drain tank switch sends
a signal to the microprocessor. The microprocessor stops all operation of the unit, flashes the
“TANK FULL” LED, indicates “TANK FL” on the LCD and closes the contact of output signal.
Ê ÊÊ Ê ÊÊÊ Ê UÊ/ÃÊÃÞÃÌiÊÕÌâiÃÊ>Êä°£Ê]Ê£ÓxÉÓxäÊ6ÊVÀÃÜÌVÊvÀÊÌÃÊvÕV̰Ê7iÊ`À>ÊÜ>ÌiÀ
accumulates approximately 8.0 gal (30 L) in the drain tanks, the drain tank base plate, which is
supported at its fulcrum, is pushed down in the arrow direction as shown in the figure below.
Ê ÊÊ Ê ÊÊÊ Ê UÊ7iÊÌiÊ`À>ÊÌ>ÊL>ÃiÊ«>ÌiÊÃÊvÀVi`Ê`Ü]ÊÌiÊÌ«ÊvÊÌiÊ`À>ÊÌ>ÊL>ÃiÊ«>ÌiÊÌÕÀÃÊvvÊÌi
contacts #1-#2 of the micro switch. This causes the ground signal at the J103 connector of the
control panel assembly to go open. When the microprocessor detects this event, it shuts the unit
off, flashes the “TANK FULL” LED, indicates “TANK FL” on the LCD and closes the contact of
output signal.
Ê ÊÊ Ê ÊÊÊ Ê UÊ7iÊÌiÊ`À>ÊÌ>ÃÊ>ÀiÊÀiÛi`ÊÀÊÌiÊ`À>ÊÌ>ÃÊ>ÀiÊi«Ìi`®]ÊÌiÊÌ«ÊvÊÌiÊ`À>ÊÌ>
base plate returns to its original position from the tension of the coil spring. Then contacts #1-#2
of the drain tank switch close. This provides a ground to the microprocessor through the J103
connector.
I002230
2
NC
C
1
DS2
DS1
Evaporator
Drain Pan
Drain Tube
Drain Tanks
Fulcrum
Drain Water
Top Base Plate
Base Plate
Base
Drain Switch
Spring
To J103