Repair Section
50
6.7 Inspection of Compressor Motor
• Measure resistance across the terminals of the
compressor motor. (All terminals must be
disconnected from the unit.)
• Between terminals (at 77 °F (25 °C))
- R-C Approx. 0.4 ohm
- C-S Approx. 0.6 ohm
- S-R Approx. 0.9 ohm
• If the measured resistance is not equal to these
standard values, replace the compressor. The
overload relay is internal to the compressor.
6.8 Thermistor Inspection
• Use an ohmmeter to check the resistance
across the 2-pin connector at normal
temperature (77 °F (25 °C)).
6.9 Wiring Connection Inspection
• While referring to the wiring diagrams, check the connection of each wire.
CAUTION
Secure the wires using clamps to prevent contact with the edges of the structure, etc. Secure the
wires in the same position as prior to removal.
Type
Specification
Characteristic
Room Thermistor (RTS) 5 k ohm at 77 °F (25 °C)
Freeze Protection Thermistor
(CTS)
5 k ohm at 77 °F (25 °C)
I001945
R
T3
S
T2
C
T1
I001695
Comentários a estes Manuais